Transistor output

Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and terminal
block.
■Differences in circuit
Sink output [-common]
Output to make load current flow into the output (Y) terminal is called sink
output.
Load
Y
COM
Fuse
DC power supply
A common number is inserted into
Handling of transistor output
■Output terminal
Module
CPU module, output
module (extension cable
type), I/O module
(extension cable type),
powered input/output
module, and high-speed
pulse input/output
module
Output module
(extension connector
type) and I/O module
(extension connector
type)
■External power supply
For driving the load, use a smoothing power supply of 5-30VDC that can output current two or more times the current rating of
the fuse connected to the load circuit.
13 WIRING
194
13.6 Output Wiring
of "COM
".
Sink output
Connect each COM (number) terminal to the minus side of
the load power supply.
The COM terminals are not connected internally.
Load
Y0
Y1
Fuse
DC power supply
COM0
Load
Y4
Y5
Fuse
DC power supply
COM1
COM (number) terminals that are connected to each other
inside the programmable controller are prepared. For external
wiring, connect the COM (number) terminals outside the
programmable controller to reduce the load per one COM
terminal.
Load
Y0
Y1
Fuse
COM0
COM0
DC power
supply
Source output [+common]
Output to make load current flow out of the output (Y) terminal is called source
output.
Load
Y
+V
Fuse
DC power supply
A common number is inserted into
Source output
Connect +V (number) terminal to the plus side of the load
power supply.
The +V terminals are not connected internally.
Load
Fuse
DC power supply
Load
Fuse
DC power supply
+V (number) terminals that are connected to each other
inside the programmable controller are prepared. For external
wiring, connect the +V (number) terminals outside the
programmable controller to reduce the load per one +V
terminal.
Load
DC power
supply
Fuse
of "+V
".
Y0
Y1
+V0
Y4
Y5
+V1
Y0
Y1
+V0
+V0