High-speed counter

Wiring examples for high-speed counters are shown below.
When capturing pulses of a response frequency of 50 to 100kHz for the FX5S/FX5UJ CPU modules or 50 to 200kHz for the
FX5U/FX5UC CPU modules, refer to the following.
Page 181 When capturing high-speed pulses
1-phase 1-input (software)
The wiring examples in this section use the following settings. When settings other than those in the table are used, use the
examples shown in the following figures as references for wiring.
Item
CH to be used
Pulse input mode
External preset input
External enable input
Operation mode
The settings of the high-speed counters are set by using the parameter settings of the engineering tool.
For details, refer to MELSEC iQ-F FX5 User's Manual (Application).
■Wiring example
NPN open collector transistor output rotary encoder
Sink wiring
When using the input of FX5U-32MT/ES
Fuse
L
Class-D grounding
N
S/S
0V
24V
1.5kΩ
X0
FX5U-
32MT/ES
For FX5UC-32MT/D
Fuse
Class-D grounding
1.5
COM
X0
FX5UC-32MT/D
*1 The grounding resistance should be 100 or less.
Rotary encoder
24VDC
24V
*1
0V
Phase A
Phase B
Phase Z
Rotary encoder
24V
24VDC
0V
*1
Phase A
Phase B
Phase Z
Setting details
CH1 (CPU module) or CH9 (high-speed pulse input/output module)
1-phase 1-input (software)
Disable
Disable
Normal mode
When using the input of FX5-16ET/ES-H
Fuse
L
Class-D grounding
N
S/S
0V
FX5U-
24V
32MT/ES
S/S
1.5kΩ
X0
FX5-
16ET/ES-H
For FX5-16ET/ES-H
Fuse
Class-D grounding
COM
FX5UC-32MT/D
FX5-CNV-IFC
S/S
1.5
X0
FX5-16ET/ES-H
13.7 Wiring Examples for Various Uses
Rotary encoder
24VDC
24V
*1
0V
Phase A
Phase B
Phase Z
Rotary encoder
24V
24VDC
0V
*1
Phase A
Phase B
Phase Z
13 WIRING