UPS Maintenance
b.
Pull the foam filter over the screw heads on the cabinet mounted studs and remove the filter from the
cabinet.
Ensure washed filters are thoroughly dry before reinstalling.
c.
Push the washed or new foam filter over the screw heads on the cabinet mounted studs until seated
against the cabinet.
d.
Reinstall the FI-UPM front panel removed in Step c and secure with the retained hardware.
4.
Record maintenance results and any corrective actions in a suitable log.

Figure 115. FI-UPM Air Filter Location

FI-UPM Air Filter
9 9 . . 2 2 . . 3 3 P P E E R R I I O O D D I I C C M M a a i i n n t t e e n n a a n n c c e e
Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to bolted connections. Maintenance procedures
should specify that the bolted connections be retorqued to values listed in this manual.
198
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14