Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 68

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

1.
Remove one top screw and two bottom screws securing the UPS left front panel (see
panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
2.
Remove the screws securing the internal safety shield panel and remove the panel to gain access to the
input, output, and battery terminals. Retain the hardware for later use.
3.
Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals.
See
Figure 15
for wiring access information and
locations or
Figure 18
through
Top Access Wiring. Remove the top conduit plate from the top of the UPS. Identify all conduit
requirements and mark their location. Drill and punch all conduit holes in the top conduit plate prior to
mounting on the UPS. Install the conduit plate and install all conduit runs into the plate. Pull the wiring
through the conduit into the wiring area.
Bottom Access Wiring. Remove the bottom conduit plate from the inside bottom of the UPS. Identify all
conduit requirements and mark their location. Drill and punch all conduit holes in the bottom conduit plate
prior to mounting on the UPS. Install the conduit plate and install all conduit runs into the plate. Pull the
wiring through conduit into the wiring area.
4.
Locate the external wiring terminal hardware kit packed on the bottom left side of the ISBM section.
5.
If installing a UPS with separate rectifier feeds, proceed to Step 6; otherwise, proceed to Step 8.
NOTE
On a UPS that is configured for separate rectifier inputs, all sources that feed the
separate rectifier inputs must be derived from a common ground point.
6.
Connect phase A, B, and C rectifier input power wiring from the utility source to each UPM rectifier input
terminal block in the UPS cabinet. See paragraph
and
Table 14
for wiring and termination requirements.
7.
Proceed to Step 11.
8.
Using hardware from the external wiring terminal hardware kit (see
rectifier input power wiring from the utility source to the rectifier input terminals in the UPS cabinet. See
paragraph
3.2.4 UPS System Power Wiring
9.
If installing a UPS configured as an Input Output Module (IOM), proceed to Step 14; otherwise, proceed to
Step 10.
10. Using hardware from the external wiring terminal hardware kit (see
and Neutral (if required) bypass input power wiring from the utility source to the bypass input terminals and
neutral terminals in the UPS cabinet. See paragraph
and termination requirements.
11. If wiring a distributed bypass system, proceed to Step 12; otherwise, proceed to Step 14.
12. Using hardware from the external wiring terminal hardware kit (see
and Neutral power wiring from the output and neutral terminals of each UPS unit to the customer-supplied
tie cabinet or load distribution panel. See paragraph
and termination requirements.
13. Proceed to paragraph
4.6.3 Battery Power Wiring
14. Using hardware from the external wiring terminal hardware kit (see Table
B, and C, and Neutral (if required) power wiring from output terminals and neutral terminals to the critical
load. See paragraph
3.2.4 UPS System Power Wiring Preparation
15. Proceed to
4.6.3 Battery Power Wiring
Figure 16
Figure 19
for separate rectifier feed terminal locations.
3.2.4 UPS System Power Wiring
Preparationfor wiring and termination requirements.
3.2.4 UPS System Power Wiring Preparation
3.2.4 UPS System Power Wiring Preparation
.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
UPS System Installation
and
Figure 17
for common rectifier feed terminal
Preparation,
Table
12), connect phase A, B, and C
Table
12), connect phase A, B, and C,
Table
12), connect phase A, B, and C,
3-11Table
12), connect phase A,
for wiring and termination requirements.
Figure
12). Lift the
Table
14,
for wiring
for wiring
47

Advertisement

Table of Contents
loading

Table of Contents