Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 153

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

UPS Operating Instructions
NOTE 1
NOTE 2
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode in approximately ten
seconds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
7 7 . . 3 3 . . 1 1 4 4 S S t t a a r r t t V V a a r r i i a a b b l l e e M M o o d d u u l l e e M M a a n n a a g g e e m m e e n n t t S S y y s s t t e e m m H H i i g g h h A A l l e e r r t t M M o o d d e e f f r r o o m m B B y y p p a a s s s s C C o o m m m m a a n n d d M M e e n n u u
To start High Alert mode:
NOTE 1
NOTE 2
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select START HIGH ALERT.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying the critical load. After
one hour the UPS transfers to Variable Module Management System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT. The UPM status
indicates ONLINE. The power module is on.
7 7 . . 3 3 . . 1 1 5 5 S S t t a a r r t t i i n n g g t t h h e e U U P P M M s s
To start the power module without transferring the critical load to Online mode:
1.
Unfasten the front door latch and swing the door open (see
NOTE
2.
*Verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
132
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
Figure 12
).
Figure
63).

Advertisement

Table of Contents
loading

Table of Contents