Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 83

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

UPS System Installation
Figure 26. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
TB1
TB2
TB3
NOTE All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.
NOTE The building alarms can be programmed to display the alarm functional name.
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used.
62
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
UPS
1
10
1
10
UPS
1
10
REPO NC
REPO Return
REPO NO
REPO Return
Battery Aux
Battery Aux Common
Battery Shunt Trip +
+ Battery Shunt Trip –
Output Contactor K3 NC Aux
Output Contactor K3 NC Aux Common
Pull Chain
Pull Chain Common
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
Building Alarm 2 Return
Building Alarm 3
Building Alarm 3 Return
Building Alarm 4
Building Alarm 4 Return
Building Alarm 5
Building Alarm 5 Return