7 7 . . 6 6 . . 1 1 S S t t a a t t u u s s I I n n d d i i c c a a t t o o r r s s
The symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED)
lamps work with the alarm horn to let you know the operating status of the UPS. See
Table 34. Status Indicators
Indicator
Status
Lit Steady
Green
Lit Steady
Yellow
Lit Steady
Yellow
Lit Steady
Lit Flashing
Red
Description
The UPS is in Online mode, operating normally. The power module is supplying power to
the critical load.
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the
Normal indicator also remains illuminated.
The UPS is in Bypass mode. The critical load is supported by the bypass source. The
Online indicator is not illuminated when the system is in Bypass mode.
The UPS has an active alarm and requires immediate attention. The screen shows the
highest priority active alarms. All alarms are accompanied by an audible horn. To silence
the horn, press any control panel pushbutton once. The Alarm indicator may be
illuminated along with other indicators.
There is a new UPS alarm condition. The indicator flashes until acknowledged by
pressing any control panel pushbutton once.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
UPS Operating Instructions
Table
34.
161