To install wiring to connections:
1.
If not already installed, install the LAN and telephone drops.
2.
Unfasten the front door latch and swing the door open (see
3.
Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes (see
4.
Reinstall the interface entry plates and install the conduit.
5.
Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards. See
Figure 29
6.
Close the front door and secure the latch.
7.
Refer to the manual supplied with the X-Slot card for operator instructions.
Figure 29. X-Slot Communication Bays
X-Slot Communication Bay 1
X-Slot Communication Bay 3
4 4 . . 8 8
I I n n s s t t a a l l l l i i n n g g a a R R E E P P O O S S w w i i t t c c h h
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed.
shows a REPO switch.
for X-Slot communication bay locations.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
UPS System Installation