UPS Operating Instructions

Figure 68. Typical System Status Screen

UPS
BYPASS
MAINTENANCE BYPASS
C
H
UPM: OFFLINE
Table 32. Typical System Status Messages
Function
UPS
Bypass
Maintenance Bypass
Charger
UPM (during startup)
UPM 1
UPM 4 (if FI-UPM is installed)
Table 33. Command Menu Operation
Function
UPS Control
Commands
124
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
SYSTEM STATUS
A
R
G
E
R
Message
Shutdown; Bypass; Online; Online with ESS; Online +VMMS; High Alert
Off; On; Available
Off; On
Charger Off; Charging
DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting;
Inverter Syncing; Ready; Online
Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online, Charger Off; Online,
Charging
Subfunction
Go to Online
Enable (Disable) Energy Saver
Enable (Disable) Var Module
Management
Start High Alert
Go to Bypass
:
SHUTDOWN
:
AVAILABLE
:
OFF
:
O
F
F
CONTROL
S
Operation
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command or
proceed to further command screens.
Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Starts High Alert mode.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.
ESC