Figure 42. J1, J2, J3, And J4 15-Pin D-Sub Connectors - Eaton Power Xpert 9395 550/275 Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

Table 28. J1 through J4 Interface Connectors
Status
UPS AVAILABLE
UPS OFFLINE
BATTERY WEAK
UTILITY FAILURE

Figure 42. J1, J2, J3, and J4 15-Pin D-Sub Connectors

5 5 . . 5 5
I I n n s s t t a a l l l l i i n n g g a a n n O O p p t t i i o o n n a a l l S S u u p p e e r r v v i i s s o o r r y y C C o o n n t t a a c c t t M M o o d d u u l l e e I I I I
To install SCM II wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See
Chapter 7 UPS Operating Instructions
2.
Perform the procedure listed in paragraph
5.1 Installing an Optional Powerware Hot Sync CAN Bridge
NOTE
3.
Securely mount the SCM II at the desired location. See
NOTE
4.
Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see
5.
Reinstall the conduit landing plate.
6.
Install conduit between the UPS and SCM II. See
J1 through J4
Pins 1 and 12
Pins 3 and 13
Pins 5 and 14
Pins 6 and 15
15-Pin D-Sub
Connectors
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the
wall. Do not use hollow wall anchors
When installing signal wiring for CAN card J3 terminals, conduit must be installed
between the device and the UPS cabinet.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
Description
Contacts are closed when the UPS is operating in Online mode or ready to
supply the load.
Contacts are open when the UPS is offline. Contacts are closed when the UPS
is operating in Online mode.
Contacts are closed when approximately two minutes of battery time remains
before the critical load is lost.
Contacts are closed when Utility Failure is detected.
for shutdown instructions.
Card.
Figure 47
Figure 47
for SCM II knockout hole location.
Installing Options and Accessories
for mounting hole locations.
Figure