UPS Maintenance
4.
Record maintenance results and any corrective actions in a suitable log.
FI-UPM Air Filter

Figure 9-3. FI-UPM Air Filter Location

9.2.3

PERIODIC Maintenance

Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to bolted connections. Maintenance procedures
should specify that the bolted connections be retorqued to values listed in this manual.
9.2.4

ANNUAL Maintenance

Annual preventive maintenance should be performed only by authorized service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.
9.2.5

BATTERY Maintenance

Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should
be performed only by authorized service personnel
®
9-6
Eaton
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09