Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 36

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

C C h h a a p p t t e e r r 3 3 U U P P S S I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n a a n n d d U U n n p p a a c c k k i i n n g g
Use the following basic sequence of steps to install the UPS:
1.
Create an installation plan for the UPS system (Chapter 3).
2.
Prepare your site for the UPS system (Chapter 3).
3.
Inspect and unpack the UPS cabinet (Chapter 3).
4.
Unload and install the UPS cabinet, and wire the system
5.
Install features, accessories, or options, as applicable
6.
Complete the Installation Checklist
7.
Have authorized service personnel perform preliminary operational checks and start up the system.
3 3 . . 1 1
C C r r e e a a t t i i n n g g a a n n I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n
Before installing the UPS system, read and understand how this manual applies to the system being installed.
Use the procedures and illustrations in paragraph
to create a logical plan for installing the system.
3 3 . . 2 2
P P r r e e p p a a r r i i n n g g t t h h e e S S i i t t e e
For the UPS system to operate at peak efficiency, the installation site should meet the environmental
parameters outlined in this manual. If the UPS is to be operated at an altitude higher than 1000m (3000 ft),
contact an Eaton service representative for important information about high altitude operation. The operating
environment must meet the weight, clearance, and environmental requirements specified.
3 3 . . 2 2 . . 1 1 G G e e n n e e r r a a l l S S t t o o r r a a g g e e R R e e q q u u i i r r e e m m e e n n t t s s f f o o r r U U P P S S E E q q u u i i p p m m e e n n t t
Equipment which cannot be immediately installed and energized should be stored in an indoor, dry, clean,
ventilated area, heated environment (i.e. an temperature and humidity controlled environment). The
storage area must be protected from rain, water, chemical agents and gases as shown in
Do not store in areas where conditions such as dampness, changes in temperature, dust, dirt, rubble,
paint, conductive particulates, or corrosive atmosphere / gases are present.
Storage temperature: -25 °C to +60 °C (-13 °F to 140 °F).
Factory installed packaging and wrapping of the equipment should not be removed until equipment is
ready to install.
Equipment should be checked periodically for any signs of deterioration. It is the responsibility of the
receiving contractor to ensure protection during storage.
Equipment should be placed on true and solid level surfaces for storage.
Have a plan for condensation and environmental mitigation prior to equipment arrival.
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on the Eaton website in section
1.9 Warranty
the UPS. Contact an Eaton service representative in advance (usually a two-week notice
is required) to reserve a preferred startup date.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
(Chapter 5 Installing Options and
(Chapter 4 UPS System
will become void. This service is offered as part of the sales contract for
3.2 Preparing the Site
(Chapter 4 UPS System
Installation).
Installation).
and
Chapter 4 UPS System Installation
Accessories).
Table
1.
15