Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 223

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

Product Specifications
1 1 0 0 . . 2 2 . . 2 2 U U P P S S O O u u t t p p u u t t
UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/ 3%)
Output Voltage Harmonic Content
Output Current
Output Voltage Balance
Output Voltage Phase Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
Overload Capability
NOTE
1 1 0 0 . . 2 2 . . 3 3 U U P P S S E E n n v v i i r r o o n n m m e e n n t t a a l l
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (Operating and Storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD) Immunity
202
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
The 110% overload capability in the above table is based on the kVA label rating of the
UPS. The 125% and 150% overloads are based on the non-derated hardware capability
of the UPS.
100% rated current
±1% (10% to 100% load)
400 Vac nominal, adjustable from 388 Vac to 412 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
See
Table 5
through
Table 9
3% for 100% maximum load imbalance (linear load)
3° for 100% maximum load imbalance (linear load)
±5% (10% to 100% load)
±0.1 Hz free running
+10% to -10% ±3%
1 Hz per second maximum
0.9 pF Leading
0.8 pF Lagging
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Maximum 1000m (3000 ft) at 40°C without derating
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self discharge)
5% to 95% maximum non-condensing
76 dB at a 1m distance, A weighted
Meets FCC Regulation 47, Part 15, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.