Table 33. Command Menu Operation (Continued)
Function
Bypass
Commands
Charger
Control
Commands
UPM Control
Commands
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
7 7 . . 3 3
S S i i n n g g l l e e U U P P S S O O p p e e r r a a t t i i o o n n
The paragraphs in this section provide operating instructions for a UPS system containing only one UPS.
NOTE
7 7 . . 3 3 . . 1 1 S S t t a a r r t t i i n n g g t t h h e e U U P P S S i i n n O O n n l l i i n n e e M M o o d d e e
To start the UPS system:
Subfunction
Load Off
Go to Bypass
Go to Online
Enable (Disable) Energy Saver
Enable (Disable) Var Module
Management
Start High Alert
Load Off
Charger On
Charger Off
UPM On
UPM Off
UPM Go to Online
Charger On
Charger Off
A Field Installed UPM (FI-UPM) is always designated as UPM 4.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
Operation
Displays the Load Off screen (see paragraph
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command or
proceed to further command screens.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.
Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Starts High Alert mode.
Displays the Load Off screen (see paragraph
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command.
Turns the battery charger on.
Turns the battery charger off.
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command.
Turns the UPM on without transferring the load to Online mode. The Load
is on bypass.
Transfers the load to bypass and turns the UPM off.
Turns the UPM on and transfers the load to Online mode.
Turns the battery charger on.
Turns the battery charger off.
UPS Operating Instructions
7.2.7 Load Off
Screen).
7.2.7 Load Off
Screen).