Table 31. Display Menu Operation (Continued)
Function
Subfunction
High Alert Timer
Variable Module
Management
System
VMMS Load Limit
VMMS UPM
Redundancy
High Alert Timer
Password
System Level 1
Setup
Function Selection
Operation
arrow pushbutton to set the time. Press SAVE or ABORT. Once the action is
completed, the Energy Saver System Setup screen is displayed.
The High Alert Timer screen sets the length of time the UPS remains in Online
mode before transferring back to Energy Saver System mode. The time can be set
in 10 minute increments from 0 to 990 minutes. Select HIGH ALERT TIMER from
the Energy Saver System Setup screen to display the High Alert Timer screen. Use
the up or down arrow pushbutton to set the time. Press SAVE or ABORT. Once the
action is completed, the Energy Saver System Setup screen is displayed.
The Module Management System Setup screen allows the Variable Module
Management System function to be configured. Select MODULE MANAGEMENT
SYSTEM SETUP from the System Setup Level 0 menu to display the Module
Management System Setup screen. Use the up or down arrow pushbutton to
highlight the desired function, then press the SELECT pushbutton. To return to the
System Setup screen, press the ESC pushbutton.
The VMMS Load Limit screen sets the maximum load that can be drawn from a
UPM before additional UPMs are activated. Select APM LOAD LIMIT from the
Module Management System Setup screen to display the VMMS Load Limit screen.
Use the up or down arrow pushbutton to set the load limit. Press SAVE or ABORT.
Once the action is completed, the Module Management System screen is
displayed.
The VMMS UPM Redundancy screen sets the number of UPMs to remain active to
maintain redundancy. Select VMMS UPM REDUNDANCY from the Module
Management System Setup screen to display the VMMS UPM Redundancy screen.
Use the up or down arrow pushbutton to set the number of UPMs. Press SAVE or
ABORT. Once the action is completed, the Module Management System Setup
screen is displayed.
The High Alert Timer screen sets the length of time the all UPMs remain active
before transferring back to Variable Module Management System mode. The time
can be set in 10 minute increments from 0 to 990 minutes. Select HIGH ALERT
TIMER from the Module Management System Setup screen to display the High
Alert Timer screen. Use the up or down arrow pushbutton to set the time. Press
SAVE or ABORT. Once the action is completed, the Module Management System
Setup screen is displayed.
The System Setup Level 1 screen can be used to set the UPS date and time, set the
serial ports, change the Level 1 password, and log out of Level 1. In addition, the
Level 0 functions are available. A password is required to access the Level 1
functions. To enter the password, select ENTER PASSWORD from the System
Setup Level 0 menu to display the Enter Password screen. Use the left or right
arrow pushbutton to select the password character position. Use the up or down
arrow pushbutton to change the password character. Once the password is entered,
press the DONE pushbutton. The System Setup Level 1 menu screen is displayed.
The default password is L1.
Use the up or down arrow pushbutton to highlight the setup function screen
desired, then press the SELECT pushbutton to display the function screen. The
Level 1 screen times out after 60 minutes or can be logged out at any time by
selecting the LOG OUT function from the menu screen.