Figure 114. UPS Filter Locations

ISBM Air Filter Locations
Ensure washed filters are thoroughly dry before reinstalling.
e.
Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seated
against the cabinet.
f.
Close the front door and secure the latch.
g.
Reinstall the UPM front panel removed in Step a and secure with the retained hardware.
h.
Reinstall the ISBM left front panel removed in Step b and secure with the retained hardware.
3.
If the Field Installed UPM (FI-UPM) is installed, check the FI-UPM air filter (located behind the front panel)
and wash or replace as necessary. See
0.25". Contact an Eaton service representative for a replacement filter. To remove the filter:
a.
Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton
9395 Field Installed UPM Mechanical Installation Manual listed in para.
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
Figure 115
for the filter location. The FI-UPM filter size is 20" x 44" x
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
UPS Maintenance
UPM Air Filter Location
1.7 For More
Information). Lift
197