Eaton Power Xpert 9395 550/275 Installation And Operation Manual page 66

Hide thumbs Also See for Power Xpert 9395 550/275:
Table of Contents

Advertisement

4 4 . . 3 3
F F i i e e l l d d I I n n s s t t a a l l l l e e d d U U P P M M I I n n s s t t a a l l l l a a t t i i o o n n
If installing a FI-UPM, install the FI-UPM using the instructions in the Eaton 9395 Field Installed UPM
Mechanical Installation Manual, listed in
4.4 Battery System Installation
4.5 Distributed Bypass Tie Cabinet
4 4 . . 4 4
B B a a t t t t e e r r y y S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n
If installing an Eaton battery cabinet, refer to the Eaton 9395 Integrated Battery Cabinet (Model IBC-L)
Installation Manual, listed in
If installing a customer-supplied battery system, install the battery system according to the battery and battery
system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
After the battery system is installed, proceed to
distributed bypass tie cabinet; otherwise, proceed to
complete the wiring of the UPS.
4 4 . . 5 5
D D i i s s t t r r i i b b u u t t e e d d B B y y p p a a s s s s T T i i e e C C a a b b i i n n e e t t I I n n s s t t a a l l l l a a t t i i o o n n
NOTE
If installing a distributed bypass system, install the customer-supplied tie cabinet or distribution panel according
to the tie cabinet or distribution panel manufacturer's instructions and all applicable codes and regulations,
including the NEC, Article 480. After the tie cabinet is installed, proceed to
4.6 Installing UPS External and Battery Power Wiring
In the case of parallel Distributed Bypass configurations, wiring for the common system neutral reference will
also be connected to E12 of each module and this common system neutral reference wiring will be routed to
the output switchgear cabinet and connected to an isolated / ungrounded bus which is common with the wiring
from the E12 terminal of all other paralleled modules of the Distributed Bypass system.
4 4 . . 6 6
I I n n s s t t a a l l l l i i n n g g U U P P S S E E x x t t e e r r n n a a l l a a n n d d B B a a t t t t e e r r y y P P o o w w e e r r W W i i r r i i n n g g
NOTE 1
NOTE 2
NOTE 3
NOTE 4
1.7 For More
if installing a battery system; otherwise, proceed to
Installation.
1.7 For More Information
4.5 Distributed Bypass Tie Cabinet Installation
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary
contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed
to go to bypass individually during servicing. All UPMs will go to bypass instead of the
just the UPM needing service, decreasing critical load protection. With dual auxiliary
MOBs, one UPM can be bypassed while the remaining UPMs support the load as long
as the remaining UPMs have the capacity to do so.
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of
the unit (see
Figure
15). Do not remove the debris shield until installation is complete.
However, remove the shield before operating the UPS. Once the debris shield is
removed, do not place objects on the ventilation grill.
Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit
holes (see
Figure
15).
If the load requires a neutral, a bypass source neutral must be provided.
DO NOT install both a source neutral and a bonding jumper. See
bonding jumper wire sizes. Bonding jumper must be copper wire.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
Information. After the FI-UPM is installed, proceed to
.
4.6 Installing UPS External and Battery Power Wiring
to complete the wiring of the UPS.
UPS System Installation
if installing a
to
Table 10
for neutral
45