UPS Installation Plan and Unpacking
Table 4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Power Xpert
9395-550/225
Power Xpert
9395-550/275
Power Xpert
9395-550/450
Power Xpert
9395-550/500
Power Xpert
9395-550/550
Figure 3. UPS Cabinet Dimensions (Front View)
1873.9
[73.8]
18
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 14
Input/Output
Rating
Voltage
400/400
225 kVA
480/480
400/400
275 kVA
480/480
400/400
450 kVA
480/480
400/400
500 kVA
480/480
400/400
550 kVA
480/480
1333.8
[52.5]
Dimensions are in millimeters [inches].
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
43 (10943)
44 (11054)
53 (13375)
54 (13510)
87 (21886)
88 (22107)
96 (24318)
Approximately 1652 liter/sec (3500
CFM)
97 (24563)
106 (26749)
107 (27020)
Ventilation Required for
Cooling Air Exhaust
Approximately 826 liter/sec (1750
CFM)