Jog Run - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

Note 5) Be aware that DC braking continues even if a startup signal is input during DC braking.
Note 6) Only F and R maintain HD (operation hold). When using F or R in combination with other
functions, be aware that the other functions do not hold. For example, when F and SS1 are
assigned, F holds, but SS1 does not.
[Parameter settings]
Terminal symbol
Title
S2

 Usage example 2 ··· Jog run
Jog run is used for inching the motor. When a jog run signal is input, a jog run frequency is immediately output,
regardless of the acceleration time set.
Assign the jog run function to any input terminal. For example, when assigned to the S2 terminal, set  =
. Jog run is done while the jog input terminal (S2 terminal) and either F or R are ON.
Setting frequency
0
F com m and
R com mand
S2 com m and
( f114=18)
Norm al operation
of frequency
setting sig nal input
● The jog frequency is fixed at 5Hz.
● The stop pattern is slowdown stop.
● The jog run setting terminal is valid when the operation frequency is less than the jog frequency. Jog run does
not function when the operation frequency is higher than the jog frequency.
● Even if an operation command is input midway, jog operation is prioritized.
● The jog frequency is not limited by the upper limit frequency ( parameter ).
Function
Input terminal selection 4A (S2)
Forward run
Forward run
Reverse run
G-5
Adjustment range
Setting example
0-201
(HD operation hold)
Forward run
E6582233
50
7 7