6.18.15 Number of starting alarm

f648 : Number of starting alarm
 Function
[Parameter setting]
f648
★ "0.1" displayed on the monitor refers to 1000 times, and therefore "1.0" denotes 10000 times.
Ex.: 38.5 displayed on the monitor = 385000 (times)
★ Display of number of starting alarm information
Number of starting alarm information (Refer to chapter 8) in the Status monitor mode allows you to check
on the time of replacement.
An example of display:
★ Output of number of starting alarm signal
The number of starting alarm is assigned to the output terminal.
6
Setup example) When the number of starting alarm is assigned to the OUT terminal
f131  Output terminal selection 2A (OUT)
Setting value 163 is reverse signal.
★ The number of starting, forward number of starting and reverse number of starting until present time can
be monitored by setting status monitor mode. (Refer to chapter 8)
★ The monitor value of the number of starting, forward number of starting and reverse number of starting
are reset to 0(zero) by setting typ = 12 (number of starting clear). (Refer to section 4.3.2)
Counting the number of starting, when it will reach the value of parameter f648 setting, it will be
displayed and alarm signal is output.
Title
Function
Number of starting alarm
 
Title
Function
Adjustment range
0.0-999.0 (10000 times)
Adjustment range
0-255
F-58
E6582233
Default setting
100.0
Setting
162: NSA (Number of
starting alarm)