[Alarm information]
Error code
A-05
A-17
A-30
ATN
CLR
DB
E-49
E-50
E-51
E1
E2
E3
EASY/
/
STD
EOFF
ERR1
/
HEAD/
END
/
HI/
LO
INIT
LSTP
12
MOFF
Note) When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter,
you can judge the inverter to be normal if "" disappears when opening the circuit between the terminal and CC.
(Continued overleaf)
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
Problem
An attempt was made to operate at a
Output frequency upper
limit
frequency higher than 10 times the base
frequency ( or ).
The RUN or STOP key is held down for
Operation panel key
alarm
more than 20 seconds.
The RUN or STOP key is faulty.
The carrier frequency() setting is
Carrier frequency
higher than 4kHz when = 2 or 3.
setting error alarm
Auto-tuning in process
Auto-tuning
This message is displayed when pressing
Clear command
acceptable
the STOP key while an error code is
displayed.
DC braking in process
DC braking
The input terminal was switched to sink
External power supply
input
logic of external power supply input
logic switching check
(+24V).
alarm
The input terminal was switched to source
Source logic switching
check alarm
logic.
The input terminal was switched to sink
Sink logic switching
check alarm
logic.
The number of digits such as frequencies
Flowing out of excess
number of digits
is more than 4.
(The upper digits have a priority.)
The EASY key was pushed in the
Switching display of
Easy setting mode /
standard monitor mode.
Standard setting mode
The operation panel is used to stop the
Emergency stop
command acceptable
operation in automatic control or remote
control mode.
The frequency setting signals at points 1
Frequency point setting
error alarm
and 2 are set too close to each other.
The first and last data item in the
Display of first/last data
items
data group is displayed.
An error is found in a setting when data is
Setting error alarm /
An error code and data
reading or writing.
are displayed
alternately twice each.
Parameters are being initialized to default
Parameters in the
process of initialization
values.
The automatic stop function selected with
Auto-stop because of
was activated.
continuous operation at
the lower-limit
frequency
The supply voltage between R, S and T is
Undervoltage in main
circuit
under voltage.
Possible causes
Operate at a frequency within 10 times the
Check the operation panel.
Check the parameter and .
Normal if it the message disappears after a
Press the STOP key again to clear the trip.
The message goes off in several tens of
Check the wiring, and set the appropriate
Check to make sure that the wiring is
Lower the frequency free unit magnification
When easy is displayed, setting mode
Press the STOP key for an emergency
Set the frequency setting signals at points 1
Press MODE key to exit the data group.
Check whether the setting is made
Normal if the message disappears after a
This function is cancelled, when frequency
Measure the main circuit supply voltage
L-4
E6582233
Remedies
base frequency.
few seconds.
seconds if no problem occurs. Note)
logic.
normal, and reset or turn the power off and
then back on again. This switches the logic.
.
becomes easy setting mode. When std
is displayed, it becomes standard setting
mode.
stop.
To cancel the emergency stop, press any
other key.
and 2 apart from each other.
correctly.
while (several seconds to several tens of
seconds).
reference reaches LL+0.2Hz or operation
command is OFF.
(between the terminal PA and PC).
If the voltage is at a normal level, the
inverter requires repairing.