7.3.1
Settings depending on voltage (0 to 10 V) input
You can set the frequency settings by inputting an analog voltage signal of 0 to 10Vdc between the VI and CC
terminals.
The following shows examples when the run command is input from the terminal.
Title
Function
Command mode selection
Frequency setting mode
selection
Analog/logic input selection
(VI terminal)
VI input point 1 setting
VI input point 1 frequency
VI input point 2 setting
VI input point 2 frequency
Analog input filter
MCCB
R/L1
Power
S/L2
Supply
T/L3
FLA
FLB
FLC
P24
OUT
NO
CC
= : Voltage signal input (0 – 10 V) (default)
Adjustment range
0 - 2
0 - 5
0: Voltage signal input (0 - 10V)
1: Current signal input (4 - 20mA)
2: Logic input
3: Voltage signal input (0 - 5V)
0 - 100%
0.0 - 400.0Hz
0 - 100%
0.0 - 400.0Hz
4 - 1000 ms
Motor
VF-nC3E
U/T1
V/T2
W/T3
S1
S2
Forward
F
run
Reverse
R
run
FM
CC
VI
P5
+
0 to 10 V
-
G-11
Default setting
1
(panel keypad)
2
(setting dial)
0
0
0.0
100
*
64
Run and stop settings
You can switch between forward run (F)
and reverser run (R), and run/stop with
IM
external signals.
Setting characteristics for the frequency
setting signal and operation frequency
Set characteristics at two points in the
diagram below.
Connecting and calibrating the
frequency meter
Select the type of meter connected at
and calibrate.
Refer to section 3.4 for details.
Hz
Point 1
0%
(0 V
Frequency setting signal
E6582233
Setting example
0
(terminal board)
0
(terminal board VI)
0
(Voltage signal
(0 – 10V))
0
0.0
100
60.0
64
7 7
Point 2
%
100%
to
10 V)