Output Terminal Function (Sink Logic); Control Terminal Block; Assign One Type Of Function To An Output Terminal - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

7.2.2

Output terminal function (sink logic)

This function is used to output a variety of signals to external devices from the inverter.
With the logic output terminal function, you can select from multiple output terminal functions. Set two types of
functions for the OUT terminal and then you can output when either one or both of them is ON.

[Control terminal block]

 Usage
FLA, B, C function: Set at parameter .
OUT function: Set at parameter  and .
Note1) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact,
etc. In particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with
input unit terminal of programmable controller. Please use the OUT terminal as much as possible when the
programmable controller is connected.
 Assign one type of function to an output terminal
Terminal
Title
symbol
OUT
 Output terminal selection 1A
FL
 Output terminal selection 2
(A, B, C)
Note 2) When assigning 1 type of function to the OUT terminal, set only .
Leave parameter  as the standard setting ( = ).
FLA FLB FLC
CC VI P5 FM
OUT NO CC F
R S1 S2 P24
Function
G-7
FLA
FLB
FL
FLC
OUT
NO
Adjustment range
Default setting
4 (Low-speed detection signal)
0 - 255
10 (Fault signal (trip output
E6582233
7 7
)
)