6.18 Protection functions

6.18.1 Setting motor electronic thermal protection

 : Motor electronic-thermal protection level 1
173 : Motor electronic-thermal protection level 2
 : Motor 150% overload detection time
 : Electronic-thermal memory
 Function
[Parameter setting]
6
Refer to section 3.4 for details.
Note 1: The 100% standard value is the rated output current indicated on the nameplate.

6.18.2 Setting of stall prevention level

 : Stall prevention level 1
 : Stall prevention level 2
 Do not set the stall prevention level (  ) extremely low.
If the stall prevention level parameter (  ) is set at or below the no-load current of the motor, the
stall preventive function will be always active and increase the frequency when it judges that
Prohibited
regenerative braking is taking place.
Do not set the stall prevention level parameter (  ) below 30% under normal use conditions.
 Function
This parameter allows selection of the appropriate electronic thermal protection characteristics
according to the particular rating and characteristics of the motor.
Title
Function
Motor electronic-thermal protection

level 1
Motor electronic-thermal protection
f173
level 2
Motor 150% overload detection time

Electrical-thermal memory
f632
This parameter adjusts the output frequency by activating a current stall prevention function against a
current exceeding the  -specified level.
Adjustment range
10-100 (%) / (A)
10-100 (%) / (A)
10-2400 (s)
0: Disabled, 1: Enabled
Caution
F-48
E6582233
Default setting
100
100
300
0