Toshiba TOSVERT VF-nC3E Instruction Manual page 45

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

Terminal
Input /
symbol
output
Output
24Vdc power output
P24
This terminal can be used as an external
Input
24Vdc input for logic input terminal by
changing parameter f127=200.
Multifunction programmable open
collector output. Standard default setting
detect and output low speed signal.
Multifunction output terminals to which
two different functions can be assigned.
The NO terminal is an isoelectric output
OUT
Output
terminal. It is insulated from the CC
NO
terminal.
By changing parameter settings, these
terminals can also be used as
multifunction programmable pulse train
output terminals.
Multifunction programmable relay contact
FLA
output.
FLB
Detects the operation of the inverter's
FLC
Output
protection function.
Contact across FLA-FLC is closed and FLB-
Note 2)
FLC is opened during protection function
operation.
Note 2) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact, etc. In
particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with input unit terminal
of programmable controller. Please use the OUT terminal as much as possible when the programmable controller is
connected.
Function
24Vdc-100mA
-
Open collector output
24Vdc-100mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
38~1600pps
Max. switching
capacity
250Vac-2A
30Vdc-2A
(cos=1)
: at resistive load
250Vac-1A
(cos=0.4)
30Vdc-1A
(L/R=7ms)
Min. permissible
load
5Vdc-100mA
24Vdc-5mA
B-9
Electrical
Inverter internal circuits
specifications
P24
protection circuit
CC
OUT
NO
FLA
FLB
FLC
E6582233
+24V
Over current
OFF:f127=200
10
+24V
RY
2 2