6.18.11 Cumulative operation time alarm setting

 : Cumulative operation time alarm setting
 Function
*
[Parameter setting]

■ Setting of output signal
Ex.: When assigning the cumulative operation alarm signal output function to the OUT terminal

6
Setting value 57 is reverse signal.

6.18.12 Undervoltage trip

 : Undervoltage trip/alarm selection
 Function
=: The inverter is stopped. However, it is not tripped (Failure signal FL not activated).
=: Inverter is stopped. It is also tripped (Failure signal FL activated), only after detection of a voltage
=: Inverter is stopped. However, it is not tripped (Failure signal FL not activated). The inverter stop
[Parameter setting]

This parameter allows you to set the inverter so that it will put out an alarm signal after a lapse of the
cumulative operation time set with .
"0.1" displayed on the monitor refers to 10 hours, and therefore "1" denotes 100 hours.
Ex.: 38.5 displayed on the monitor = 3850 (hours)
Title
Function
Cumulative operation time
alarm setting
Title
Function
Output terminal selection
1A (OUT)
This parameter is used for selecting the control mode when an undervoltage is detected. Trip
information is displayed as "".
The inverter is stopped when the voltage does not exceed 64 % or less of its rating.
not exceeding 64% or less of its rating.
(Failure signal FL not activated.), only after detection of a voltage not exceeding 50% of its rating.
Be sure to connect the input AC reactor specified in section 9.4.
Title
Function
Undervoltage trip/alarm
selection
Adjustment range
0.0-999.0
Adjustment range
0-255
56: COT (Cumulative operation time alarm)
Adjustment range
0: Alarm only (detection level 64% or less)
1: Tripping (detection level 64% or less)
2: Alarm only (detection level 50% or less,
input AC reactor required)
F-56
E6582233
Default setting
610.0
Setting
Default setting
0