6.10

Jog run mode

 : Jog run frequency
 : Jog run stop pattern
 : Operation panel jog run mode
• Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run
frequency output at once, irrespective of the designated acceleration time.
Also, you can choose an operation panel start/stop mode between the ordinary start/stop mode and the jog
run start/stop mode.
The jog run function needs to be assigned to an input terminal.
When assigning it to the S3 terminal, set  to .
The motor can be operated in jog run mode while the jog run setting terminals are connected (S3-CC: ON).
[Parameter setting]
Title
Jog run frequency

Jog run stop pattern

Operation panel jog run mode

<Examples of jog run>
S3-CC (JOG) ON + F-CC ON: Forward jog run
S3-CC (JOG) ON + R-CC ON: Reverse jog run
( Normal operation frequency signal input + F-CC ON: Forward run, Normal operation frequency signal input + R-CC ON: Reverse run )
Output frequency [Hz]
Set frequency
0
ST-CC
F-CC
R-CC
S3-CC
Input of operation
frequency setting signal
• The jog run setting terminal (S3-CC) is enabled when the operation frequency is below the jog run frequency.
This connection does not function at an operation frequency exceeding the jog run frequency.
• The motor can be operated in jog mode while the jog run setting terminals are connected (S3-CC: ON).
• Jog run has priority, even when a new operation command is given during operation.
• In operation panel operation mode (), setting the parameter  (input terminal priority selection) at 
makes it possible to perform jog run, using RUN and STOP keys.
• Even for = or , an emergency DC braking becomes enabled when setting =.
• If parameter  (selection of priority when forward and reverse run signals are input simultaneously) is set to
 (reverse run), the jog run frequency is not limited by the upper limit frequency (UL) even when forward and
reverse run signals are input simultaneously. Operation modes switch as follows: Forward jog run → Deceleration
stop (jog frequency → 0Hz) → Reverse jog run, please be careful.
Function
~Hz
:Deceleration stop, : Coast stop,
:DC braking stop
:OFF,
:Operation panel jog run mode enabled
Forward
Forward
Forward run
run
run
Reverse
run
F-19
Adjustment range
E6581301
Default setting

6