[Parameter setting]
Title

Small current detection hysteresis

Small current trip/alarm selection
Small current detection current


Small current detection time
<Example of operation>

Output terminal function: 26 (UC) Low current detection

f610 = 0 (Alarm only)
Low current
signal output
Output current (%)
 + 

*
When setting f610 to 1 (Trip), trip after low current detection time setting of f612 . After tripping,
the low current signal remains ON.

6.18.8 Detection of output short-circuit

 : Detection of output short-circuit at start-up
 Function
This parameter detects inverter output short-circuit. It can be usually detected in the length of the
standard pulse. When operating low-impedance motor such as high-speed motor, however, select the
short-time pulse.
 =  : Detection is executed in the length of the standard pulse every time you start up the inverter.
 =  : Detection is executed in the length of standard pulse only during the first start-up after putting on
the power or after resetting.
 =  : Detection is executed with the short-time pulse every time you start up the inverter.
 =  : Detection is executed with the short-time pulse only for the first time after putting power on or
after resetting.
Function
 or less
F-53
Adjustment range
1-20 (%)
0: Alarm only
1: Tripping
0-150 (%) / (A)
0-255 (s)
ON
OFF

Time [sec]
E6582233
Default setting
10
0
0
0
OFF
6