Parameter Registration To Easy Setting Mode; Communication Function (Rs485) - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

6.20.8 Parameter registration to easy setting mode

 -  : Easy setting mode parameter 1 to 24
Up to 24 arbitrary parameters can be registered to easy setting mode.
 Refer to section 4.4 for details.

6.21 Communication function (RS485)

 : Baud rate
 : Parity
 : Inverter number
 : Communication time-out time
 : Communication time-out action
 : Communication time-out
6
 : Selection of communication
 Set the parameter Communication time-out time ( f803 ) and Communication time-out action ( f804 ).
If these are not properly set, the inverter cannot be stopped immediately in breaking communication and
this could result in injury and accidents.
 An emergency stop device and the interlock that fit with system specifications must be installed.
Mandatory
If these are not properly installed, the inverter cannot be stopped immediately and this could result in
action
injury and accidents.
Refer to the Communications Function Instruction Manual (E6581657) for details.
 Function
2-wire RS485 communication is built-in as standard.
Connect with the host to create a network for transmitting data between multiple inverters. A computer
link function is available.
<Computer-linking functions>
 Timer function
 Broadcast communication function
detection condition
protocol
The following functions are enabled by data communication between the computer and inverter
(1) Monitoring inverter status (such as the output frequency, current, and voltage)
(2) Sending RUN, STOP and other control commands to the inverter
(3) Reading, editing and writing inverter parameter settings
 : Block write data 1 
 : Block write data 2
 : Block read data 1
 : Block read data 2
 : Block read data 3
 : Block read data 4
 : Block read data 5
Warning
... Function used to detect cable interruptions during communication.
When data is not sent even once to the inverter during a user-
defined period of time, an inverter trip ( is displayed on the
panel) or an output terminal alarm can be output.
... Function used to send a command (data write) to multiple
inverters with a single communication.
F-68
E6582233