Toshiba TOSVERT VF-nC3E Instruction Manual page 209

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

Communicati
Ti tle
 FMSL
FM

FR

ACC

DEC

FH

UL

LL

VL

10
VLV

PT

VB

THR

*1: Default setting values vary depending on the capacity. Refer to section 10.4.
Function
Unit
on No.
0005
Meter selection
0006
Meter adjustment
gain
0008
Forward/reverse
run selection
(Panel keypad)
0009
Acceleration time
1
0010
Deceleration time
1
0011
Maximum
frequency
0012
Upper limit
frequency
0013
Lower limit
frequency
0014
Base frequency 1
0409
Base frequency
voltage 1
0015
V/F control mode
selection
0016
Torque boost
value 1
0600
Motor electronic-
thermal protection
level 1
Minimum
setting unit
Adjustment range
Panel/Comm
unication
-
-
0: Output frequency
1: Output current
2: Frequency reference
3: Input voltage (DC detection)
4: Output voltage (command value)
5 to 11: -
12: Frequency setting value (after
compensation)
13: VI input value
14: -
15: Fixed output 1
(output current 100% equivalent)
16: Fixed output 2
(output current 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: RS485 communication data
19: For adjustments ( set value is
displayed.)
20 to 22: -
-
-
-
-
-
0: Forward run
1: Reverse run
2: Forward run (F/R switching on
extension panel)
3: Reverse run (F/R switching on
extension panel)
S
0.1/0.1
0.0-3000
S
0.1/0.1
0.0-3000
Hz
0.1/0.01
30.0-400.0
Hz
0.1/0.01
0.5- 
Hz
0.1/0.01
0.0- 
Hz
0.1/0.01
20.0-400.0
V
1/0.1
50-660
-
-
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5 to 6: -
7: V/F 5 point setting
%
0.1/0.1
0.0-30.0
%
1/1
10-100
(A)
J-2
E6582233
Default
User
Reference
setting
setting
0
3.3
-
0
5.7
10.0
5.3
10.0
50
5.8
50
5.9
0.0
50
5.10
400
5.10
6.13.6
0
5.11
* 1
5.12
100
3.4
6.18.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents