7.2
Applied operations by an I/O signal (operation from
the terminal block)
7.2.1
This function is used to send a signal to the input terminal from an external programmable controller to operate or
configure the inverter.
The ability to select from a variety of functions allows for flexible system design.
[Control terminal board]
7
Settings for the logic input terminal function
Terminal
symbol
F
R
S1
S2
VI
Note 1) Multiple functions assigned to a single terminal operate simultaneously.
Note 2) In case of setting always active function, assign the menu number to and (always active
function selection).
Note 3) When VI is used for the logic input, always connect a resistor between VI and terminal P24 in sink logic,
between VI and terminal CC in source logic. Refer to section 2.3.2 (page B-12) for details.
Input terminal function
FLA FLB FLC
OUT NO CC F
Title
Function
Input terminal selection 1A (F)
Input terminal selection 1B (F)
Input terminal selection 1C (F)
Input terminal selection 2A (R)
Input terminal selection 2B (R)
Input terminal selection 2C (R)
Input terminal selection 3A (S1)
Input terminal selection 3B (S1)
Input terminal selection 4A (S2)
Input terminal selection 4B (S2)
Analog/logic input
Selection (VI terminal)
Input terminal selection 5 (VI)
CC VI P5 FM
R S1 S2 P24
Adjustment range
0-201 Note 1)
0-201 Note 1)
0-201 Note 1)
0-201 Note 1)
0: Voltage signal input (0 - 10 V)
1: Current signal input (4 - 20 mA)
2: Logic input
3: Voltage signal input (0 - 5 V)
8-55 Note 3)
G-2
E6582233
Default setting
2 (F)
0 (No function)
0 (No function)
4 (R)
0 (No function)
0 (No function)
10 (SS1)
0 (No function)
12 (SS2)
0 (No function)
0
14 (SS3)