Over-Torque Trip; Over-Torque Trip/Alarm Selection; Over-Torque Detection Level; Over-Torque Detection Time - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

[Parameter setting]


6.18.9 Over-torque trip

 : Over-torque trip/alarm selection
 : Over-torque detection level
 : Over-torque detection time
 : Over-torque detection hysteresis
 Function
6
 =  : .......... No tripping (FL relay deactivated).
 =  : .......... The inverter is tripped (FL relay activated) only after a torque exceeding the  -
[Parameter setting]




Note:  = 0.0 seconds is the shortest time detected on control.
Function
Title
Detection of output short-circuit at
start-up
If the torque value exceeds the value set at  and doesn't return below  - 
for a time that exceeds the value set at  , tripping or output alarm will be activated.
 is displayed in the event of a trip.
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
specified level has been detected for more than the  -specified time.
Title
Function

Over-torque trip/alarm selection

Over-torque detection level

Over-torque detection time

Over-torque detection hysteresis
Adjustment range
0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
Adjustment range
0: Alarm only
1: Tripping
0 (disabled),
1-200(%)
0.0-10.0 (s)
Note
0-100 (%)
F-54
E6582233
Default setting
0
Default setting
0
150
0.5
10