9. Peripheral devices

 When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Mandatory
action
 Connect grounding cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.
Be Grounded
9.1

Selection of wiring materials and devices

 Selection of cable size
Voltage class
3 phase
400V class
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,
V/T2 and W/T3 when the length of each wire does not exceed 30m.
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The cable sizes specified in the above table apply to HIV cables (copper cables shielded with an insulator
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
Power circuit
Applicable
(Note 1, 5)
motor (kW)
For Japan
IEC
(JEAC800
compliant
1-2005)
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
3.7
2.5
2.0
5.5
4.0
2.0
7.5
6.0
3.5
11
10.0
5.5
Warning
2
Cable size (mm
) (Note 4)
Braking resistor
(optional)
For Japan
IEC
(JEAC800
compliant
compliant
1-2005)
-
-
-
-
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
2.5
2.0
4.0
2.0
2
or more in diameter.
I-1
E6582233
Grounding cable
For Japan
IEC
(JEAC800
1-2005)
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
6.0
3.5
10.0
5.5
9