The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:
 Calorific values of the inverter and the required ventilation
1
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class
Three-phase
400V class
*1
Note1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input
Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values
Inverter type
4kHz
4004P
20
4007P
28
4015P
51
4022P
64
VFNC3E
4037P
106
4055P
139
4075P
195
4110P
270
It is power consumption when power is on but is not output (0Hz), and cooling fan is activated.
reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table.
Amount of forcible air
cooling ventilation
3
required (m
/min)
12kHz
4kHz
12kHz
23
0.11
0.13
27
0.16
0.16
67
0.29
0.38
74
0.37
0.42
140
0.60
0.79
156
0.79
0.89
264
1.11
1.50
288
1.53
1.64
A-22
E6582233
Heat discharge surface
Standby power
area required for sealed
requirement
3
storage cabinet (m
)
(W)
*1
4kHz
12kHz
0.39
0.47
8
0.56
0.55
8
1.01
1.34
10
1.29
1.47
10
2.12
2.79
12
2.78
3.13
13
3.91
5.28
21
5.41
5.77
23