Physical Specifications - Huawei FusionServer Pro XH321 V5 Maintenance And Service Manual

Server node
Hide thumbs Also See for FusionServer Pro XH321 V5:
Table of Contents

Advertisement

FusionServer Pro XH321 V5 Server Node
Maintenance and Service Guide
Category
Altitude
Corrosive gaseous
contaminant
Particle contaminant

3.3 Physical Specifications

Table 3-3 Physical specifications
Category
Dimensions (H x W x
D)
Weight in full
configuration
Power consumption
Issue 17 (2021-03-09)
Specifications
● Operating altitude ≤ 3050 m (10006.44 ft)
If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft) in
altitude above 900 m (2952.76 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
● Titanium PSUs are required for the altitude higher
than 3050 m (10006.44 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the
equipment room be monitored by a professional agency.
Description
40.5 mm x 177.9 mm x 545.5 mm (1.59 in. x 7.00 in. x
17.89 in.)
● Net weight: 4.2 kg (9.26 lb)
● Packing material weight: 2.73 kg (6.02 lb)
The power consumption parameters vary with
hardware configurations (including the configurations
complying with EU ErP). Use the
Power Calculator
Copyright © Huawei Technologies Co., Ltd.
3 Product Specifications
Computing Product
to obtain specific information.
28

Advertisement

Table of Contents
loading

Table of Contents