Selection Of Operating Mode - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Building Technologies
8

Selection of operating mode

To facilitate straightforward adaptation of the LMV27 to different types of burners, the
LMV27 offers automatic configuration of the operating mode. This means that – derived
from parameter 201 – the most important settings relating to the operating mode are
made automatically. Very often in that case, the only manual settings to be made are
those for the air-fuel ratio control system. After selection of the operating mode,
parameters that are not required will be hidden (e.g. oil parameters when firing on gas).
No.
Parameter
Burner operating mode (fuel train, modulating / multistage, actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
201
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod separate circulation control
24 = Ho 2-stage separate circulation control
25 = Ho mod without circulation control
26 = Ho 2-stage without circulation control
27 = Ho 3-stage without circulation control
28 = G mod mech air actuator only
29 = Gp2 mod mech air actuator only
¹) Selected operating mode is not released for the LMV27.
With select: Error code 210 diagnostic code 0
Basic Documentation LMV27...
8 Selection of operating mode
¹)
¹)
¹)
¹)
¹)
¹)
¹)
79/219
CC1P7541en
17.12.2018