Makeup Of Error History - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Deleting the error history
116/219
Building Technologies
18.2

Makeup of error history

Parameter
Index
701
.01
.02
.03
.04
.05
.06
702
.01..06
725
.01..06
No.
Parameter
166
Total number of startups
Both the service menu and the parameter setting menu show the error history.
The display on the service menu can be deleted in a way that the only errors shown are
those that occurred after the deletion. The error history on the parameter setting menu
cannot be deleted.
For the deletion, parameter 130 must be set to 1 and then to 2 within 6 seconds.
When the parameter returns to 0, the deletion process is completed.
No.
Parameter
Delete display of error history
To delete the display: Set the parameter to 1, then to 2.
130
Response 0: Job successfully
Response: -1: Timeout of 1_2-Sequence
Basic Documentation LMV27...
18 Error history
Description
Current error state, can also be error-free
Error code (200 = error-free)  refer to chapter Error code
list
Diagnostic code  refer to chapter Error code list
Error class  error classes
Error phase: Phase in which error occurred  sequence
diagrams
Startup counter. Startup meter reading (parameter 166) at
which the error occurred
Power: Burner output at which the error occurred
Latest error in the history
Oldest error in the history
CC1P7541en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents