If it is not only the current curvepoint that shall be changed, but all other curvepoints in the direction of
travel as well, a new straight line from the current curvepoint to P9 (press
be calculated by a long push on
Display CALC
Building Technologies
P
>3 s
or
Example of presentation
CALC -
Figure 83: Changing several curvepoints
Note
Due to interpolation, a number of curvepoints change. To be able to make a
check on the burner itself, the changed curvepoints must be approached in
the warm settings. If these curvepoints have not yet been completely
approached, OFF UPr appears on the normal display of the AZL2.
Basic Documentation LMV27...
26 Parameter level
V
h min s
%
.
CALC +
>3 s
) or P1 (press
P5 up to P9
Keep
depressed for >3 s
P5 down to P1
Keep
depressed for >3 s
CC1P7541en
) can
173/219
17.12.2018