Siemens LMV27.100x2 Basic Documentation page 182

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
Index 1 = output external load controller analog
Index 2 = Power of external load controller contacts
124
Start loss-of-flame test (TÜV test) (set parameter to 1)
(shutdown of fuel valves  loss of flame)
Error diagnostics via negative values (see error code 150)
125
Mains frequency
0 = 50 Hz
1 = 60 Hz
126
Display brightness
127
Timeout via menu operation
128
Fuel meter: Pulse valency [pulses / volume unit]
130
Delete display of error history
To delete the display: Set the parameter to 1, then to 2
Response 0: Job successful
Response: -1: Timeout of 1_2-Sequence
133
Default output at TÜV test
Invalid = TÜV test at active output
20...100 = low-fire...high-fire or stage 1 / stage 2 / stage 3
P1...P3 = stage 1...stage 3
141
Operating mode building automation
0 = off
1 = Modbus
2 = reserved
142
Setback time in the event of communication breakdown
Setting value:
0 = deactivated
1...7200 s
143
Reserved
144
Reserved
Device address for Modbus of LMV27
145
Setting values
1...247
146
Setting of Baud rate for Modbus communication
0 = 9600
1 = 19200
182/219
Building Technologies
Number of
Type
Edit
elements
1
Std_s8
Edit
1
Selection
Edit
1
Std_u8
Edit
1
Std_u8
Edit
1
Std_u16
Edit
1
Std_s8
Edit
1
Power
Edit / clear
1
Selection
Edit
1
Std_u16
Edit
1
Std_u8
Edit
1
Std_u16
Edit
1
Std_u8
Edit
1
Selection
Edit
Basic Documentation LMV27...
27 Parameter list
Value range
Increment
Min.
Max.
-6
1
1
0
1
1
0%
100%
1%
10 min
120 min
1 min
0
400
0,01
-5
2
1
20%
100%
0,1%
0
2
1
0 s
7200 s
1 s
1
8
1
10 s
60 s
1 s
1
247
1
0
1
1
Default
Password level
setting
Write
Read
1
1%
2
0%
0
HF
HF
0
HF
HF
75%
HF
HF
30 min
OEM
OEM
0
HF
HF
0
HF
HF
undefined
HF
HF
0
HF
HF
120 s
HF (GA)
HF (GA)
1
HF
IS
30 s
HF
HF
1
HF
HF
1
HF
HF
CC1P7541en
17.12.2018