Siemens LMV27.100x2 Basic Documentation page 204

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Error
Diagnostic code
code
1 Pressure switch max / POC
2 Pressure switch valve proving
3 Air pressure
4 Load controller open
5 Load controller on/off
6 Load controller close
7 Safety loop / Burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve V1
11 Fuel valve V2
12 Fuel valve V3
13 Reset
106
#
0 Pressure switch min
1 Pressure switch max / POC
2 Pressure switch valve proving
3 Air pressure
4 Load controller open
5 Load controller on/off
6 Load controller close
7 Safety loop / Burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve V1
11 Fuel valve V2
12 Fuel valve V3
13 Reset
107
#
0 Pressure switch min
1 Pressure switch max / POC
2 Pressure switch valve proving
3 Air pressure
4 Load controller open
5 Load controller on/off
6 Load controller close
7 Safety loop / Burner flange
8 Safety valve
204/219
Building Technologies
Meaning for the LMV27
Internal error contact request
Internal error contact request
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
diagnostic code indicates the input where the problem occurred
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
CC1P7541en
17.12.2018