Siemens LMV27.100x2 Basic Documentation page 166

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Example 1 = gas modulating
P0, P1 and P9 are set as described:
P2 through P8 have automatically been
calculated:
166/219
Building Technologies
Figure 82: Setting the curvepoints
Note
Curvepoints P2 to P8 are automatically calculated as a straight line between P1 and
P9.
Basic Documentation LMV27...
26 Parameter level
Curvepoints
Curvepoint
Value 1
fuel
P0
30.0
P1
32.0
P9
80.0
Curvepoint
Value 1
fuel
P2
38.0
P3
44.0
P4
50.0
P5
56.0
P6
62.0
P7
68.0
P8
74.0
Air
Fuel
Value 2
air
22.0
24.0
90.0
Value 2
air
32.3
40.5
48.8
57
65.3
73.5
81.8
CC1P7541en