Error
Diagnostic code
code
Bit 3
Valency 8..15
Bit 4
Valency 16..31
202
#
203
#
204
Phase number
205
#
206
0
207
#
0
1
208
#
209
#
210
0
240
#
242
#
0
1
245
#
250
#
Building Technologies
Meaning for the LMV27
Standardized speed undefined
Backup / restore was not possible
Internal error operating mode selection
Internal error
Program stop
Internal error
Inadmissible combination of LMV27
(LMV27 - AZL2)
Version compatibility LMV27 - AZL2
LMV27 version too old
AZL2 version too old
Internal error
Internal error
Selected operating mode is not released for the LMV27
Internal error
Invalid parameterization
Invalid setting parameter 277
Invalid setting parameter 377
Internal error
Internal error
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
Carry out speed standardization.
If no speed signal is present in pneumatic operation, the parameters 667, 668, 669.0 / 669.1 must
be set to invalid to switch off the start prevention.
Redefine the operating mode (parameter 201)
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the LMV27
Program stop is active (no error)
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
Select a released operating mode for the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
Set parameter 277 to a valid value
Set parameter 377 to a valid value
Make a reset; if error occurs repeatedly, replace the LMV27
Make a reset; if error occurs repeatedly, replace the LMV27
209/219
CC1P7541en
17.12.2018