Error
Diagnostic code
code
21
#
0
1
64
22 OFF
#
S
0
1
3
5
17
19
21
23
65
67
69
71
81
83
85
87
23
#
0
1
2
Building Technologies
Meaning for the LMV27
Pressure switch-max / POC
Pressure switch-max : Max. gas / oil pressure exceeded
POC: POC open (software version
V02.00)
POC close (software version
V02.00)
POC open - start prevention (software version
Safety loop / burner flange
Safety loop / burner flange open
Safety loop / burner flange open - start prevention
Safety loop/burner flange, extraneous light – start prevention
Safety loop/burner flange, air pressure – start prevention
Safety loop/burner flange, combustion pressure – start
prevention
Safety loop/burner flange, extraneous light, combustion
pressure – start prevention
Safety loop/burner flange, air pressure, combustion pressure –
start prevention
Safety loop/burner flange, extraneous light, air pressure,
combustion pressure – start prevention
Safety loop/burner flange, POC – start prevention
Safety loop/burner flange, extraneous light, POC – start
prevention
Safety loop/burner flange, air pressure, POC – start prevention
Safety loop/burner flange, extraneous light, air pressure, POC
– start prevention
Safety loop/burner flange, combustion pressure, POC – start
prevention
Safety loop/burner flange, extraneous light, combustion
pressure, POC – start prevention
Safety loop/burner flange, air pressure, combustion pressure,
POC – start prevention
Safety loop/burner flange, extraneous light, air pressure,
combustion pressure, POC – start prevention
Gas pressure switch-min / heavy oil direct start
No minimum gas pressure
Gas shortage – start prevention
Heavy oil direct start
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
Check wiring to see if there is a line interruption.
POC: Check to see if the valve's closing contact is closed.
Check wiring
Check to see if the valve's closing contact opens when the valve is controlled
Check wiring
V02.00)
Check to see if the valve's closing contact opens when the valve is controlled
Check wiring to see if there is an open-circuit (X5-01)
Check wiring to see if there is an open-circuit (X5-01)
Check wiring to see if there is an open-circuit (X9-04)
195/219