Error
Diagnostic code
code
Bit 4
Valency
16
Bit 5
Valency
32
Bit 6
Valency
64
Bit 7
Valency
128
84
#
200/219
Building Technologies
Meaning for the LMV27
Interruption of speed signal
Quick shutdown due to excessive speed deviation
Minimum speed fall below (phase-dependent)
Maximum speed exceeded (phase-dependent)
Curve slope actuators
Basic Documentation LMV27...
28 Error code list (of all LMV2 / LMV3 types)
Recommended measures or causes
Curve slope max. 10% for LMV27 ramp of 20 seconds (20% for 10 seconds or 40% for 5
seconds)
2. Modulating operating ramp 48 seconds
Curve slope max. 10% for LMV27 ramp of 30 seconds (20% for 15 seconds or 30% for 10
seconds)
3. Modulating operating ramp 64 seconds
Curve slope max. 10% for LMV27 ramp of 40 seconds (20% for 20 seconds or 40% for 10
seconds)
→ Between the ignition point (P0) and the low-fire point (P1), the speed change in modulating
mode may be a maximum of 40%, independent of the LMV27 ramp.
4. The setting of the VSD ramp must be about 20% faster than the ramps in the LMV27
(parameters 522, 523).
No speed detected in spite of control.
1. Check if the motor turns.
2. Check if the speed sensor delivers a signal (LED / check distance from the sensor disk).
3. Check wiring of the VSD.
Speed deviation was for about 1 s >10% outside the anticipated range.
1. Check ramp times of the LMV27 and VSD.
2. Check wiring of the VSD.
1. Standby (phase 12): Check the setting for the minimum speed and maximum speed during
operation (parameter 669.0 / 669.1; MAX > MIN).
2. Check the speed recording (absolute speed parameter 935, standardized speed parameter
936).
3. Prepurge phase (phase 30): Read-in speed or prepurge speed (parameter 503.1 / 506.1) below
the minimum speed for prepurging (parameter 667).
4. Operating phases (phase 40...64): Read-in speed or setting of the speed curve below the
minimum speed in operation (parameter 669.0).
1. Standby (phase 12): Setting preignition time (parameter gas 226 / 336 or oil 266 / 366) at least
 parameter 665)
3 seconds (or
2. Standby (phase 12): Check the setting for the minimum speed and maximum speed during
operation (parameter 669.0 / 669.1; MAX > MIN).
3. Check the speed recording (absolute speed parameter 935, standardized speed parameter
936).
4. Preignition time (phase 38): Read-in speed or setting of the ignition speed (P0) above the
maximum speed for ignition (parameter 668).
5. Operating phases (phase 40...64): Read-in speed or setting of the speed curve above the
maximum speed in operation (parameter 669.1).
CC1P7541en
17.12.2018