Siemens LMV27.100x2 Basic Documentation page 185

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod separate circulation control ¹)
24 = Ho 2-stage separate circulation control ¹)
25 = Ho mod. without circulation control ¹)
26 = Ho 2-stage without circulation control ¹)
27 = Ho 3-stage without circulation control ¹)
28 = G mod mech air actuator only ¹)
29 = Gp2 mod mech air actuator only ¹)
¹) Selected operating mode is not released for the LMV27:
With select: Error code 210 diagnostic code 0
Function Load controller contacts staged
205
0 = standard
1 = stages interchanged
208
Program stop
0 = deactivated
1 = prepurge position (phase 24)
2 = ignition position (phase 36)
3 = interval 1 (phase 44)
4 = interval 2 (phase 52)
210
Alarm in the event of start prevention
0 = deactivated
1 = activated
211
Fan ramp up time
212
Maximum time down to low-fire
213
Waiting time until home run
214
Maximum time start release
215
Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
Every 24 hours
217
Maximum waiting time for detection of detector or pressure
Building Technologies
Number of
Type
Edit
elements
1
Std_u8
Edit
1
Selection
Edit
1
Selection
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Std_u8
Edit
1
Time
Edit
Basic Documentation LMV27...
27 Parameter list
Value range
Increment
Min.
Max.
0
1
1
0
4
1
0
1
1
2 s
60 s
0,2 s
0,2 s
10 min
0,2 s
2 s
60 s
0,2 s
0,2 s
10 min
0,2 s
1
16
1
5 s
10 min
0,2 s
Default
Password level
setting
Write
Read
0
OEM
OEM
0
HF (GA)
HF (GA)
0
HF
HF
2 s
HF
HF
45 s
HF
HF
2 s
OEM
OEM
25 s
OEM
OEM
16
HF
HF
30 s
OEM
OEM
185/219
CC1P7541en
17.12.2018