Fuel Throughput; Configuration; Reading Out The Fuel Throughput - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

110/219
Building Technologies

13.2 Fuel throughput

With the fuel meter connected, the LMV27 calculates continuously the current fuel
throughput. The time required for calculating the fuel throughput varies and lies between
1 and 10 seconds. If the fuel meter delivers no pulses for more than 10 seconds, the
display shows 0 fuel throughput. This means that when fuel throughput is at its
minimum, the sensor should have a pulse frequency of at least 0.1 Hz. The display is
smoothed to improve the settling process. With fuel throughput at its maximum, the
maximum frequency is 300 Hz.

13.2.1 Configuration

Calculation of fuel throughput is configured based on the pulse valency of the connected
fuel meter.
No.
Parameter
128
Fuel meter: Pulse valency (pulses/volume unit)
When the pulse valency is set to 0.00, the display shows 0 throughput.

13.2.2 Reading out the fuel throughput

The current fuel throughput can be read out via the following parameter on the service
menu:
No.
Parameter
960
Fuel throughput in volume unit /h (m³/h, l/h, ft³/h, gal/h)
Display of fuel throughput is possible up to 6553 volume units/h.
Note
Display of fuel throughput up to a value of 99.9 on the service menu is made with one
decimal place, from 100 with no decimal place.
Basic Documentation LMV27...
13 Fuel meter input X75 pin 1 / X75 pin 2
CC1P7541en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents