Siemens LMV27.100x2 Basic Documentation page 190

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
Setting values:
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1)
3 = both
613
Type of actuator
Index 0 = fuel
Index 1 = air
Setting values:
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
645
Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
700
Error history
701
Current error state
701.01
Error code
701.02
Diagnostic code
701.03
Error class
701.04
Error phase
701.05
Startup counter
701.06
Output
702
Latest error in the history
725
Oldest error in the history
900
Process data
903
Current output
Index 0 = fuel
Index 1 = air
922
Incremental position of actuators
Index 0 = fuel
190/219
Building Technologies
Number of
Type
Edit
elements
2
Std_u8
Edit
1
Std_u8
Edit
25
Std_u8
Read only
25
Std_u8
Read only
25
Std_u8
Read only
25
Std_u8
Read only
25
Std_s32
Read only
25
Output
Read only
2
Output
Read only
2
Std_s16
Read only
Basic Documentation LMV27...
27 Parameter list
Value range
Increment
Min.
Max.
0
2
1
0
2
1
0
255
1
0
255
1
0
6
1
0
255
1
0
99999999
1
0%
100%
0,1%
0%
100%
0,1%
-50°
150°
0,01°
Default
Password level
setting
Write
Read
0; 0
OEM
HF
0
OEM
HF
0
---
IS
0
---
IS
0
---
IS
0
---
IS
0
---
IS
0%
---
IS
0%
---
IS
For query
via
ACS410
---
IS
CC1P7541en
17.12.2018