Siemens LMV27.100x2 Basic Documentation page 102

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

102/219
Building Technologies
Example of actuator with counterclockwise rotation:
When referencing in the CLOSE position, the actuator first travels a certain distance into
the working range (towards the OPEN position). Then, it travels to a position
representing maximum -7.7°, thereby crossing the reference mark for the first time.
Then, the actuator moves in the other direction again and detects the inner ramp of the
reference mark. This is the reference point used by all positions. If the reference point is
parameterized in the OPEN position, referencing takes place in a mirror-symmetrical
manner. In that case, the actuator first travels into the working range (toward the OPEN
position). Then, it crosses the reference mark and travels to a position representing
maximum 110.6°, then back to the inner ramp of the reference mark.
Figure 68: Angle definitions with SQM33
Error
Diagnostic
code
code
85
0
1
Bit 7
Valency ≥128
Basic Documentation LMV27...
11 Actuators X53 / X54
Close (0°
Range stop "Open"
Reference range "Open"
Meaning for the LMV27
Referencing error of fuel actuator
Referencing error of air actuator
Referencing error due to parameter change
Reference range "Close"
7.7°
0.6°)
Range stop "Close"
CC1P7541en
17.12.2018