21.6.2 Restore

Building Technologies
Basic Documentation LMV27...
21 Operating via AZL2 unit
Parameter 000: flashes.
Display: Parameter 000: flashes, Int does not.
/reset
Press
to select parameter 050
Display: Parameter 050. flashes, index 00: and value 0 do
not.
/reset
Press
to go to parameter bAC_UP.
/reset
Display: Parameter bAC_UP
Press
to go to the rEStorE function.
Display: Parameter rEStorE
/reset
Press
to select the restore process.
/reset
Display: Value 0
Press
to shift the value in change mode 1 position to
the left.
Display: Value 1 flashes.
Note
To detect potential display errors, the value is displayed 1
place shifted to the left.
125/219
CC1P7541en
17.12.2018