Ignition; Postpurging - Siemens LMV27.100x2 Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Table of Contents

Advertisement

90/219
Building Technologies
10.2.4

Ignition

The ignition position is approached in phase Traveling to the ignition position (38).
The position is set via curve parameterization under P0. In modulating operation, this
point is assigned to an output of 10%.
10.2.5

Postpurging

This position is approached in phase Traveling to postpurging (72).
The position can be set via the following parameters:
Parameter
Actuator
501.02
Postpurge position fuel actuator
502.02
Postpurge position air actuator
Basic Documentation LMV27...
10 Electronic air-fuel ratio control
CC1P7541en